User Manual
 Card Setup 
Sealevel Systems ULTRA-485 Page 9 
Line Termination 
Typically, each end of the RS-485 bus must have line terminating resistors (RS-
422 terminates at the receive end only). A 100-ohm resistor is across each RS-
530/422/485 input in addition to a 1K ohm pull-up/pull-down combination that 
biases the receiver inputs. DIP-switch SW2 provides the ability to customize this 
interface to system requirements. Each switch position corresponds to a specific 
portion of the interface. If multiple ULTRA 485  adapters are configured in a 
RS-485 network, only the boards on each end should have switches T, P & P 
ON. Refer to the following table for each position’s operation: 
Name Function 
T  Adds or removes the 100 ohm termination. 
P  Adds or removes the 1K ohm pull-down resistor in the 
RS-422/RS-485 receiver circuit (Receive data only). 
P  Adds or removes the 1K ohm pull-up resistor in the RS-422/RS-
485 receiver circuit (Receive data only). 
L  Connects the TX+ to RX+ for RS-485 two-wire operation. 
L  Connects the TX- to RX- for RS-485 two-wire operation. 
Figure 8 - SW2, Line Termination 
1 2 3 4 5
ON
OFF
T P P L L