IMO Technical Brochure

Leaders in Solar Safety
54
FireRaptor Overview
The IMO FireRaptor provides three forms of Solar Panel Rapid Shutdown to ZERO VOLTS in case of re or other emergency:
The FireRaptor can be installed without any set-up and with any string inverter as its functionality is completely independent. “Plug & Play”
style installation using industry standard connectors is easy, whether tted to new installs or retro-tted to existing projects to upgrade re
safety functionality.
The FireRaptor meets the current requirements of
®
2017
MANUAL EMERGENCY SHUTDOWN
Manual shutdown is operated via an Emergency Rapid Shutdown Switch utilising a typical “one push” large emergency push button. The
switch can be conveniently located anywhere for emergency access and is supplied with a 24VDC power supply to interface with the
FireRaptor units.
AUTOMATIC EMERGENCY TEMPERATURE SHUTDOWN
Automatic shutdown occurs via the temperature sensor onboard the FireRaptor detecting an ambient temperature rise in excess of 85°C
(185°F). In the event that the temperature exceeds 85°C (185°F) the FireRaptor will act to shut-down the PV panels as follows:-
FRS-01 - Shuts down the panels connected to the individual FireRaptor sensing the temperature rise above 85°C (185°F). The FireRaptor
will re-engage the panels if the temperature drops back below 85°C (185°F) provided it does not exceed 92°C (198°F), in which case a
manual reset of the Emergency Switch is required.
FRS-02 - Shuts down the entire string in which the individual FireRaptor sensing the temperature rise above 92°C (198°F) is connected.
If this occurs a signal is sent to the Emergency Switch and resetting of the Emergency Switch is then required by a professional installer.
The Emergency Switch can be congured to provide connection to the building’s central alarm system or notication via mobile
commincation (SMS, email etc.).
AUTOMATIC EMERGENCY EXTERNAL POWER LOSS SHUTDOWN
Disconnection of the external AC supply, by whatever means, causes automatic remote operation of the Emergency Rapid Shutdown
Switch.
Part Number Description
FRS-01 FireRaptor Rapid Shutdown Unit - suitable for connection to two solar panels
FRS-02 FireRaptor Monitored Rapid Shutdown Unit - suitable for connection to two solar panels
FRS-ESW1 Emergency Rapid Shutdown Switch IP66 (for FRS-01) - includes 24VDC power supply
FRS-ESW1-K Emergency Rapid Shutdown Switch IP66 (for FRS-01) with Key Lock - includes 24VDC power supply
FRS-ESW2 Emergency Rapid Shutdown Switch IP66 (for FRS-02) - includes 24VDC power supply
FRS-ESW2-K Emergency Rapid Shutdown Switch IP66 (for FRS-02) with Key Lock - includes 24VDC power supply
FRS-SIGCAB1.8-F 1.8m (70”) Signal Cable terminated at one end with Tyco female connector for use at end of PV String
Ordering Information
Solar Panel Rapid Shutdown
Manual Panel Shutdown to 0V Operated from Ground Level
Automatic Panel Shutdown to 0V at >85°C (185°F) Temperature
Automatic Panel Shutdown to 0V on External Power Loss
Hardwire or Mobile Communication Alarm Signalling
Compliant with NEC 2017 and NEC 2020
Suitable for New Installations or Retro-Fit
®
2020