Catalog Screw Figure Wire Range Bolt Dimensions Hex
Number Type Number Copper Size C D E F G H T Size
SLU-25 1 10-14 #6 5/32 9/32 7/16 1 3/16 5/16 21/32 Slot
SLU-35 1 6-14 & List Comb. (A) #10 13/64 7/16 15/32 1-3/16 7/32 3/8 3/4 Slot
SLU-35DB 1 6-14 & List Comb. (A) #10 13/64 7/16 15/32 1-3/16 7/32 3/8 3/4 Slot
SAU-70 1 4-14 1/4 17/64 7/16 17/32 1-5/16 1/4 3/8 13/16 Slot
SLU-70 1 2-8 & List Comb. (B) 1/4 17/64 1/2 21/32 1-17/32 1/4 1/2 1 Slot
SLU-70DB 1 2-8 & List Comb. (B) 1/4 17/64 1/2 21/32 1-17/32 1/4 1/2 1 Slot
SLU-125 1 1/0-6 1/4 17/64 5/8 13/16 1-31/32 7/16 5/8 1-11/32 Slot
SLU-175 1 3/0-4 3/8 13/32 3/4 15/16 2-3/16 7/16 3/4 1-9/16 3/16
SLU-225 1 4/0-2 5/16 11/32 1 1-5/32 2-5/8 1/2 1 1-13/16 7/32
SLU-300 1 350kcmil-1/0 3/8 13/32 1-1/4 1-1/2 3-3/16 1/2 1 2-5/8 5/16
SLU-400 1 500kcmil-1/0 3/8 13/32 1-1/2 1-15/16 4-14 15/16 1-1/2 2-3/4 5/16
SLU-650 1 1000kcmil-600kcmil 1/2 17/32 1-7/8 1-7/8 4-5/8 1-7/64 2 3-11/16 3/8
SLS-25 2 10-14 #6 5/32 9/32 19/32 61/64 3/16 5/16 19/32 Slot
SLS-35 2 6-14 & List Comb. (A) #10 13/64 7/16 41/64 1-9/64 7/32 3/8 11/16 Slot
SAS-70 2 4-14 1/4 17/64 7/16 23/32 1-1/4 1/4 1/2 27/32 Slot
SLS-70 2 2-8 & List Comb. (B) 1/4 17/64 1/2 13/16 1-15/32 1/4 1/2 31/32 Slot
SLS-70-TN* 2 2-8 & List Comb. (B) 1/4 17/64 1/2 13/16 1-15/32 1/4 1/2 31/32 Slot
SLS-125 2 1/0-6 1/4 17/64 5/8 1-3/16 1-15/16 7/16 5/8 1-1/4 Slot
SLS-175 2 3/0-4 3/8 13/32 3/4 1-1/4 2-3/16 7/16 3/4 1-9/16 3/16
SLS-225 2 4/0-2 5/16 11/32 1 1-7/32 2-3/8 1/2 1 1-21/32 7/32
SLS-300 2 350kcmil-1/0 3/8 13/32 1-1/4 1-1/2 3-3/16 1/2 1 2-3/8 5/16
SLS-400 2 500kcmil-1/0 3/8 13/32 1-1/2 2-3/16 3-7/8 15/16 1-1/2 2-9/16 5/16
SLS-650 2 1000kcmil-600kcmil 1/2 17/32 1-7/8 3 5-1/8 1-3/16 2 3-11/16 3/8
Copper Mechanical Lugs
One Conductor, One Hole
TYPE
SLU
SLS
SAS
SAU
Features
•
Manufactured from electrolytic copper tubing and strip
stock
•
Compact design
•
Range taking
•
Re-usable
•
Suitable for use in circuits rated 35KV or less, proper
high voltage spacing and insulation techniques must be
used
•
V-bottom collar
•
SLU-35DB and SLU-70DB are UL 467 Listed and suit-
able for direct burial
•
Rated to 90˚ C
Fig. 1 Fig. 2
Benefits
•
Provides maximum conductivity and strength
•
Saves space and reduces installation time
•
Permits inventories to be kept to a minimum
•
Provides efficient use and flexibility in the field
•
Application versatility
•
Wires are wedged between arched pressure bar and collar
establishing positive contact and firm permanent grip
453G
L
R
-
2
9
6
0
1
* Tin Plated
All wire sizes, unless noted otherwise, are American Wire Gauge (AWG)
(A) UL Listed wire combinations: (2) #10; (2) #12; (2) #14; (1) #12 and (1) #14; (1) #10 and (1) #12
(B) UL Listed wire combinations: (1) #8 and (1) #4; (1) #8 and (1) #6; (2) #4; (3) #8; (3) #6; (2) #8 and (1) #4; (2) #8 and (1) #6; (1) #6 and (1) #4; (2) #6
Tested to UL 486A/B, UL File E6207