120
Catalog Number Figure Main Wire Bottom Tap Dimensions Hex Size
Connector Number Range Range H W D Main Tap
PTA2-500-500-W/C 1 Two: 500kcmil-250kcmil Two: 500kcmil-4 3-15/16 3-1/2 1-1/4 3/8 3/8
PTA2-750-500-W/C 1 Two: 750kcmil-350kcmil Two: 500kcmil-4 3-5/8 4-3/32 1-5/16 3/8 3/8
PTA4-750-500-W/C 2 Four: 750kcmil-350kcmil Two: 500kcmil-4 5-7/8 4-3/32 1-5/16 3/8 3/8
PTA26-500-4/0*+ 3 Two: 500kcmil-4/0
Four: 4/0-6 3-15/16 3-1/2 1-1/4 3/8
5/16
Two: 2-14 Slotted
Multiple Tap Connector
Dual Rated
TYPE
PTA
Features
Manufactured from high strength 6061-T6 aluminum
alloy
Electro-tin plated
UL Listed and CSA Certified for 600 volts, 90˚ C
Compact design
Range taking
Re-usable
Lay-in main conductors
Supplied with insulating cover
Fig. 1 Fig. 2 Fig. 3
Benefits
Suitable for use with either copper or aluminum
conductors
Provides low contact resistance
Ensures reliability for copper or aluminum conductors
Saves space and reduces installation time
Permits inventories to be kept to a minimum
Provides efficient use and flexibility in the field
No need to break the feeder cables
Eliminates taping
All wire sizes, unless noted otherwise, are American Wire Gauge (AWG)
Note: W/C indicates product is supplied with insulating cover.
* Not CSA Certified.
+ Cover must be ordered separately. For non UL cover, order 1 each RO614WOOA and RO615WOOA.
DE-OX Inhibitor is recommended for all aluminum terminations.
Tested to UL 486A/B, UL File E6207