It is difficult to establish rules but globally 3 cases may arise:
CASE 1 : Ideal case: unique echo (test in lab or if the sensor front flat water surface for example)
A simple calibration would be possible.
CASE 2 : Case of a classic manhole with an invert channel in the bottom. The figure bellow shows two
echoes (the invert and the water). A calibration in advanced mode will be possible. First, check that the
sensor is
well positioned, fronting and perpendicular to the water.