Instruction Manual
99
• Monitor Data (available only for read out)
Register No. bit Description
0020H
Status signal
0 Run command 1 : Run 0 : Stop
1 Reverse run 1 : Reverse run 0 : Forward run
2 Inverter operation ready 1 : Ready 0 : Not ready
3 Fault 1 : Fault
4 Data setting error 1 : Error
5 Multi-function output 1 (1 : MA ON 0 : MA OFF)
6 Multi-function output 2 (1 : P1 ON 0 : OFF)
7 Multi-function output 3 (1 : P2 ON 0 : OFF)
8-F (Not used)
0021H
Fault description
0 Over current (OC)
1 Over voltage (OV)
2 Inverter overload (OL2)
3 Inverter overheat (OH)
4 (Not used)
5 (Not used)
6 PID Feedback loss (FbL)
7 External fault (EF, EFO) Emergency stop (STP)
8 Hardware fault (Fxx)
9 Motor overload (OL1)
A Overtorque detection (OL3)
B (Not used)
C Power loss (UV1)
D Control power fault (UV2)
E MEMOBUS communications timeover (CE)
F Operator connection (OPR)
0022H
Data link status
0 Data write in
1 (Not used)
2 (Not used)
3 Upper/lower limit fault
4 Consistency fault
5-F (Not used)
0023H Frequency reference (Unit : n152)
0024H Output frequency (Unit : n152)
0025H-026H (Not used)
0027H Output current (10/1A)
0028H Output voltage reference (1/1V)
0029H
Fault contents
0 Load short circuit (SC)
1 Ground fault (GF)
2 Input open phase (PF)
3 Output open phase (LF)
4 Installed type braking resistor overheat
5 Braking transistor fault (RR)
6-F Not used