Instruction Manual

94
Setting necessary parameters for communication
Communication related parameters must be set for PLC communication. parameters
n151 to n157 cannot be set during communication. Always set them prior to
performing communication.
* The slave does not respond to the command from the master when set to 0.
Monitoring run status from the PLC, setting/referencing of parameters, fault reset and
multi-function input reference can be done regardless of run command or frequency
reference selection.
Multi-function input reference from PLC becomes OR with input commands from S1
to S7 multi-function input terminals.
Parameter Name Description
Initial
Setting
n003 Run command selection
0 : operator
1 : control circuit terminals
2 : communication
3 : communication card (optional)
0
n004
Frequency reference
selection
0 : Local potentiometer (digital operator)
1 : frequency ref. 1 (n024)
2 : control circuit terminals (voltage 0 to 10V)
3 : control circuit terminals (current 4 to 20mA)
4 : control circuit terminals (current 0 to 20mA)
5 : pulse train
6 : MEMOBUS communication (Register No. 000211)
7 : operator circuit terminals (voltage 0 to 10V)
8 : operator circuit terminals (current 4 to 20mA)
9 : communication card (optional)
0
n151
Timeover detection
selection
Monitors transmission time
between the receiving the
correct data from the PLC
(Timeover: 2 sec)
0 : timeover detection (free run stop)
1 : timeover detection (coasting to a stop with speed
reduction time 1)
2 : timeover detection (coasting to a stop with speed
reduction time 2)
3 : timeover detection (continuous operation, warning
display)
4 : timeover detection not provided
0
n152
Communication frequency
Reference monitor unit
selection
0 : 0.1Hz
1 : 0:0.1Hz
2 : 30000/100% (30000 = max. output frequency)
3 : 0.1%
0
n153 Slave address Setting range: 0 to 32* 0
n154 Baud rate selection
0 : 2400 bps
1 : 4800 bps
2 : 9600 bps
3 : 19200 bps
2
n155 Parity selection
0 : even parity
1 : odd parity
2 : no parity
0
n156 Sending waiting time Setting limit: 10 ms to 65 ms setting unit: 1 ms 10 ms
n157 RTS control
0 : RTS control
1 : no RTS control (RS-422A 1 to 1 communication)
0