Instruction Manual

85
Frequency Reference by Pulse Train Input
Frequency reference can be set by pulse train input from the multi-function input
terminal.
Input pulse specifications
Low-level voltage: 0.8V or less
High-level voltage: 3.5 to 32V
Duty Cycle: 30 to 70%
Pulse frequency: 0 to 33 kHz
Frequency reference method
Frequency reference is a value obtained by multiplying the ratio of the maximum
input pulse frequency and actual input pulse frequency by the maximum output
frequency.
Parameter
No.
Name Unit Setting range Initial Setting
n003 Run command selection 1 0 to 2 0
n004 Frequency reference selection 1 0 to 6 0
n149 Pulse train input scaling 1=10Hz 1
100 to 3300
(33kHz)
2500
(25kHz)
Reference freq
Input pulse frequency
Minimum pulse train frequency (n149) 10
×
---------- --------- ------------- ------------ ------------- ------------ ------------ ------------- --------- ----------
max output frequency (n011)
×
=
Run/stop and FWD/REV can
be selected by a switch
connected to the control circuit
terminal.
Frequency setting can be set
by pulse train input signal [0 to
100% (maximum frequency)/0
to 33kHz] connected to the
multi-function input terminal.