Initial setting
Terminal function at 3-wire sequence selection
When 0 is set at the terminal S3 (n052), terminal S1 becomes run command, terminal
S2 becomes stop command, and terminal S3 becomes FWD/REV run command.
• LOCAL/REMOTE select (setting: 17)
Select operation reference either by the digital operator or by the settings of
operation method selection (n003) and frequency reference selection (n004).
LOCAL/REMOTE select is available only during stop.
Open: Run according to the setting of run command selection (n003) or
frequency reference selection (n004)
Closed: Run by frequency reference and run command from the digital operator.
No. Terminal Initial Setting Function
n050 S1 1 Forward run command (2-wire sequence)
n051 S2 2 Reverse run command (3-wire sequence)
n052 S3 3 External fault
n053 S4 5 Fault reset
n054 S5 6 Multi-step speed reference 1
n055 S6 7 Multi-step speed reference 2
n056 S7 10 JOG command