Instruction Manual

73
Building Interface Circuits with External Devices
Multi-function input terminal S1 to S7 functions can be changed when necessary by
setting parameters n051 or n052 respectively. The same value cannot be set to different
parameter settings.
* Numbers 1 to 7 are displayed in corresponding to the terminal number S1 to S7 respectively.
Using input signals
Setting Name Description Ref.
0
FWD/REV run command
(3 wire sequence selection)
Setting enabled only for n052 74
1
Forward run
(2 wire sequence selection)
45
2
Reverse run
(2 wire sequence selection)
45
3 External fault (NO contact input)
Inverter stops by external fault signal input
Digital operator display is
.*
4 External fault (NC contact input)
5Fault Reset
Resets the fault. Fault reset not
effective with the run signal ON.
50
6 Multi-step speed reference 1 50
7 Multi-step speed reference 2 50
8 Multi-step speed reference 3 50
9 Multi-step speed reference 4 50
10 JOG command 51
11 Accel/Decel time select 54
12
External baseblock
(NO contact input)
Motor coast to a stop by this
signal input.
Digital operator display is
13
External baseblock
(NC contact input)
14
Search command from
maximum frequency
Speed search
reference signal
63
15
Search command from
set frequency
63
16 Accel/decel hold command 64
17 LOCAL/REMOTE selection 46
18
Communication/control circuit
terminal selection
78
19
Emergency stop fault
(NO contact input)
Inverter stops by emergency stop signal input
according to stopping method selection (n005).
When frequency coasting to a stop (n005 is set
to 1) method is selected, inverter coasts to a
stop according to decel time setting 2 (n022).
Digital operator display is
(lit at fault, blinking at alarm).
20
Emergency stop alarm
(NO contact input)
21
Emergency stop fault
(NC contact input)
22
Emergency stop alarm
(NC contact input)
23 PID Control cancel 114
24 PID integral reset 114
26 Inverter overheat prediction OH3
(Blinking) is displayed on the
digital operator by signal input
25 PID intregal hold 114
34 UP/DOWN command
Setting enabled only for
n056 (terminal S7)
75
35 Self-test
Setting enabled only for
n056 (terminal S7)
114