Instruction Manual

69
Reducing Motor Noise or Leakage Current (n080)
Frequency setting varies according to inverter capacity (kVA).
(1) Reduce continuous output current when changing carrier frequency to
4 (10kHz) for the 200V class (1.5 W or more) and 400V class invert-
ers. Refer to the table above for the reduced current.
[Operation Condition]
•Input power supply voltage : 3-phase 200 to 230 V (200V class)
Single-Phase 200 to 240V (200V class)
3-Phase 380 to 460V (400V class)
•Ambient temperature: 14 to 122ºF (-10 to +50ºC)
(Protection structure: open chassis type
IP20)
(2) If the wiring distance is long, reduce the inverter carrier frequency as
described below
Voltage Class (V)
Capacity
(kW)
Initial Setting Maximum
Continuous
Output Current
(A)
Reduced
Current (A)
Setting
Carrier
Frequency
200
Single-phase 3-
phase
0.1 4 10kHz 0.8
0.2 4 10kHz 1.6
0.4 4 10kHz 3.0
0.7 4 10kHz 5.0
1.5 3 7.5kHz 8.0 7.0
2.2 3 7.5kHz 11.0 10.0
3.7 3 7.5kHz 17.5 16.5
5.5 3 7.5kHz 25 23
7.5 3 7.5kHz 33 30
400
3-phase
0.2 3 7.5kHz 1.2 1.0
0.4 3 7.5kHz 1.8 1.6
0.7 3 7.5kHz 3.4 3.0
1.5 3 7.5kHz 4.8 4.0
2.2 3 7.5kHz 5.5 4.8
3.0 3 7.5kHz 7.2 6.3
3.7 3 7.5kHz 8.6 8.1
5.5 3 7.5kHz 14.8 *
7.5 3 7.5kHz 18 17
Wiring Distance between
Inverter and Motor
Up to 50m Up to 100m More than 100m
Carrier frequency
(n080 setting)
10kHz or less
(n080=1, 2, 3, 4, 7, 8, 9)
5kHz or less
(n080=1, 2, 7, 8, 9)
2.5kHz or less
(n080=1, 7, 8, 9,)