Instruction Manual

55
n018 setting
Notes: Parameter n018 can be set during stop.
If the numeric value exceeded 600.0 sec. is set for the accel/decel time when n018 = 0 (in units
of 0.1 sec.). “1” cannot be set to n018.
Accel time
Set the time needed for output frequency to reach 100% from 0%.
Decel time
Set the time needed for output frequency to reach 0% from 100%.
(Maximum output frequency n011 = 100%)
When parameter n081 is set to 1 or 2, operation automatically restarts even if
momentary power loss occurs.
* Hold the operation command to continue the operation after recovery from a momentary power
loss.
= When 2 is selected, the inverter restarts if power supply voltage recovers while the control power
supply is held.
No fault signal is output.
No. Name Unit Setting Range Initial setting
n019 Accel time 1
Refer to
n018
setting
Refer to n018
setting
10.0s
n020 Decel time 1 10.0s
n021 Accel time 2 10.0s
n022 Decel time 2 10.0s
No. Unit Setting Range
n018
0
0.1s 0.0 - 999.9s (999.9s or less)
1s 1000 - 6000s (1000s or more)
1
0.01s 0.00 - 99.99s (99.99s or less)
0.1s 100.0 - 600.0s (100s or more)
Automatic restart after momentary power loss (n081)
Setting. Description
0 Continuous operation after momentary power loss not provided.
1*
Continuous operation after power recovery within momentary
power loss ride thru time 0.5s.
2*
=
Continuous operation after power recovery (Fault output not
provided)