Instruction Manual
166
• 200V class single-phase
• 400V class 3-phase
* Values of motor line-to-line resistance are set to half of the standard value.
= Values between V/f mode and Vector control mode.
No. Name Unit Factory setting
– Inverter capacity kW 0.1kW 0.25kW 0.55kW 1.1kW 1.5kW 2.2kW – 3.7kW 5.5kW 7.5kW
n036 Motor rated current A 0.6 1.1 1.9 3.3 6.2 8.5 – 14.1 9.8 13.3
n105
Torque
compensation iron
loss
W 1.7 3.4 4.2 6.5 11.1 11.8 – 19 28.8 43.9
n106 Motor rated slip Hz 2.5 2.6 2.9 2.5 2.6 2.9 – 3.3 1.5 1.3
n107
Motor resistance for
one phase*
Ω
17.99 10.28 4.573 2.575 1.233 0.8 – 0.385 0.797 0.443
n108
Motor leak
inductance
MH 110.4 56.08 42.21 19.07 13.4 9.81 – 6.34 16.87 10.59
n110
Motor no-load
current
% 72 73 62 55 45 35 – 32 26 30
No. Name Unit Factory setting
– Inverter capacity kW – 0.37kW 0.55kW 1.1kW 1.5kW 2.2kW 3.0kW 3.7kW 5.5kW 7.5kW
n036 Motor rated current A – 0.6 1.0 1.6 3.1 4.2 7.0 7.0 9.8 13.3
n105
Torque
compensation iron
loss
W – 3.4 4.0 6.1 11.0 11.7 19.3 19.3 28.8 43.9
n106 Motor rated slip Hz – 2.5 2.7 2.6 2.5 3.0 3.2 3.2 1.5 1.3
n107
Motor resistance for
one phase*
Ω
– 41.97 19.08 11.22 5.044 3.244 1.514 1.514 0.797 0.443
n108
Motor leak
inductance
MH – 224.3 168.8 80.76 53.25 40.03 24.84 24.84 16.87 10.59
n110
Motor no-load
current
% – 73 63 52 45 35 33 33 26 30