Instruction Manual

163
127 017F Frequency reference 16
0.00 to
400.0Hz
0.01Hz (less
than 100Hz) /
0.1Hz (100Hz
or more)
0.00Hz 51
128 0180 PID control selection 0 to 8 1 0 110
129 0181 PID feedback gain 0.00 to 10.00 0.01 1.00 113
130 0182 Proportional gain (P) 0.0 to 25.0 0.1 1.0 111
131 0183 Integral time (I) 0.0 to 360.0 0.1s 1.0 111
132 0184 Derivative time (D) 0.00 to 2.50 0.01s 0.00 111
133 0185 PID offset adjustment -100 to 100% 1% 0% 112
134 0186 Integral (I) upper limit -100 to 100% 1% 100% 112
135 0187
PID output primary delay
parameter time
0.0 to 10.0 0.1s 0.0 112
136 0188
PID feedback loss
detection selection
0,1,2 1 0 113
137 0189
PID feedback loss
detection level
0 to 100% 1% 0% 113
138 018A
PID feedback loss
detection time
0.0 to 25.5 0.1s 1.0 113
139 018B
Energy-saving control
selection (V/f control
mode)
0,1 1 0 105
140 018C
Energy-saving
coefficient K2
0.0 to 6550 0.1 (Note 7) 105
141 018D
Energy-saving voltage
lower limiter (at 60 Hz)
0 to 120% 1% 50% 106
142 018E
Energy-saving voltage
lower limiter (at 6 Hz)
0 to 25% 1% 12% 106
143 018F Power average time 1 to 200 1 = 24ms 1 (24ms) 107
144 0190
Search operation voltage
limit
0 to 100% 1% 0% 107
145 0191
Search operation voltage
step (at 100%)
0.1 to 100% 0.1% 0.5% 107
146 0192
Search operation voltage
step (at 5%)
0.1 to 10.0% 0.1% 0.2% 107
149 0195 Pulse train input scaling 100 to 3300 1 (1 = 10Hz)
2500
(25kHz)
85
150 0196
Pulse monitor output
frequency selection
0,1,6,12,24,36 --- 0 66
No.
Register
No. for
Trans-
mission
Name Setting Range
Setting
Unit
Initial
Setting
User
Setting
Ref.
Page