Instruction Manual

156
024 0118
Frequency reference 1
(Master speed frequency
reference)
0.00 to
400.0Hz
0.01Hz (less
than 100Hz) /
0.1Hz (100Hz
or more)
6.00Hz 50
025 0119 Frequency reference 2
0.00 to
400.0Hz
0.01Hz (less
than 100Hz) /
0.1Hz (100Hz
or more)
0.00Hz 50
026 011A Frequency reference 3
0.00 to
400.0Hz
0.01Hz (less
than 100Hz) /
0.1Hz (100Hz
or more)
0.00Hz 50
027 011B Frequency reference 4
0.00 to
400.0Hz
0.01Hz (less
than 100Hz) /
0.1Hz (100Hz
or more)
0.00Hz 50
028 011C Frequency reference 5
0.00 to
400.0Hz
0.01Hz (less
than 100Hz) /
0.1Hz (100Hz
or more)
0.00Hz 50
029 011D Frequency reference 6
0.00 to
400.0Hz
0.01Hz (less
than 100Hz) /
0.1Hz (100Hz
or more)
0.00Hz 50
030 011E Frequency reference 7
0.00 to
400.0Hz
0.01Hz (less
than 100Hz) /
0.1Hz (100Hz
or more)
0.00Hz 50
031 011F Frequency reference 8
0.00 to
400.0Hz
0.01Hz (less
than 100Hz) /
0.1Hz (100Hz
or more)
0.00Hz 50
032 0120 Jog frequency reference
0.00 to
400.0Hz
0.01Hz (less
than 100Hz) /
0.1Hz (100Hz
or more)
6.00Hz 51
033 0121
Frequency reference
upper limit
0 to 110% 1% 100% 54
034 0122
Frequency reference
lower limit
0 to 110% 1% 0% 54
035 0123
Unit Selection for
frequency reference
setting/display
0 to 3999 1 0 125
036 0124 Motor rated current
0 to 150% of
inverter rated
current
0.1A (Note 3) 90
037 0125
Electronic thermal motor
protection
0, 1, 2 1 0 90
038 0126
Parameter selection at
electronic thermal motor
protection
1 to 60 min 1 min 8 min 90
039 0127
Cooling fan operation
selection
0, 1 1 0 92
No.
Register
No. for
Trans-
mission
Name Setting Range
Setting
Unit
Initial
Setting
User
Setting
Ref.
Page