Instruction Manual

155
First Functions (Parameters n001 to n049)
No.
Register
No. for
Trans-
mission
Name Setting Range
Setting
Unit
Initial
Setting
User
Setting
Ref.
Page
001 0101H
Parameter write-in
prohibit / initialize
0 to 4, 6, 8, 9,
12, 13
11 39
002 0102
Control mode selection (Note
6)
0,1 1
0 (Note 1)
(Note 6) 40
003 0103
Operation reference
selection
0 to 3 1 0 47
004 0104
Frequency reference
selection
0 to 9 1 1 48
005 0105
Stopping method
selection
0, 1 1 0 71
006 0106 REV run prohibit 0, 1 1 0 50
007 0107
Operation stop enable/
disable selection
0, 1 1 0 70
008 0108
Frequency reference
selection
in local mode
0, 1 1 1 (Note 5) 48
009 0109
Setting method selection
for frequency reference
0, 1 1 0 48
010 010A
Detecting selection of
operator connecting fault
0, 1 1 0 47
011 010B
Maximum output
frequency
50.0 to
400.0Hz
0.1Hz 50.0Hz 40
012 010C Maximum voltage
0.1 to 255.0V (0.2
to 510.0)
0.1V
200.0V (Note
2)
40
013 010D
Maximum voltage output
frequency
0.2 to 400.0Hz 0.1Hz 50.0Hz 40
014 010E Mid. output frequency 0.1 to 399.9 0.1Hz 1.3Hz 40
015 010F
Mid. output frequency
voltage
0.1 to 255.0V
0.1V
12.0V
(Note 2)
40
016 0110
Minimum output
frequency
0.1 to 10.0Hz 0.1Hz 1.3Hz 40
017 0111
Minimum output
frequency voltage
0.1 to 50.0V
0.1V
12.0V
(Note 2)
40
018 0112
Accel / decel time setting
unit
0,1 1 0 55
019 0113 Acceleration time 1 0.00 to 6000s
Depend on
n018 setting
10.0s 55
020 0114 Deceleration time 1 0.00 to 6000s
Depend on
n018 setting
10.0s 55
021 0115 Acceleration time 2 0.00 to 6000s
Depend on
n018 setting
10.0s 55
022 0116 Deceleration time 2 0.00 to 6000s
Depend on
n018 setting
10.0s 55
023 0117
S-curve accel / decel
selection
0 to 3 1 0 56