Surge suppressors
Ground fault interrupter:
Select a ground fault interrupter not affected by high frequencies. To prevent
malfunctions, the current should be 200mA or more and the operating time 0.1 sec.
or more.
Example:• NV series by Mitsubishi Electric Co., Ltd. (manufactured in 1988 and
after)
• EGSG series by Fuji Electric Co., Ltd. (manufactured in 1984 and after)
AC and DC reactor:
Install an AC reactor to connect to a power supply transformer of large capacity
(600kVA or more) or to improve power factor on the power supply side.
Noise filter:
Use a noise filter exclusively for inverter if radio noise generated from the inverter
causes other control devices to malfunction.
For the details of the peripheral devices, refer to the catalog.
Parameter List
Addition of parameters accompanied by the upgraded software version
The parameters marked with #1 and #2 are applicable for the following upgraded
software version Nos.:
#1: Applicable for software version No. VSP 010015 or later
#1: Applicable for software version No. VSP 010020 or later
Parameters that can be changed during operation
The parameters whose numbers are in bold can be changed during operation.
Model
DCR2-
Specifications Code No.
200V
to
230V
Large size magnetic contactors 50A22E
250VAC
0.5
µ
F 200
C002417
Control relays
MY-2, -3 (OMRON)
HH-22, -23 (FUJI)
MM-2, -4 (OMRON)
10A25C
250VAC
0.1
µ
F 100
C002482
NOTE
(1) Never connect a general LC/RC noise filter to the inverter output circuit.
(2) Do not connect a phase advancing capacitor to the I/O sides and/or a surge
suppressor to the output side.
(3) When a magnetic contactor is installed between the inverter and the motor,
do not turn it ON/OFF during operation.
Surge Suppressors
Coils and relays