Instruction Manual

144
Other Functions
Display
Status Indicator LED RUN and ALARM provided as standard LEDs
Digital Operator
(JVOP-140)
Available to monitor frequency reference, output
frequency, output current
Ter min als
Main circuit: screw terminals
Control circuit: plug-in screw terminal
Wiring Distance between
Inverter and Motor
328ft (100m) or less#
Enclosure
Open chassis IP20, Open chassis IP20 (Top-closed type),
or enclosed wall-mounted NEMA 1
Cooling Method
Cooling fan is provided for the following models: 400V,
1.5kW or larger inverters (3-Phase)
Others models are self-cooling
Environmental
Conditions
Ambient Temperature
Open chassis IP20 : -10 to +50
°
C (14 to 122
°
F)
Open chassis IP20 (Top-closed type) and enclosed
wall mounted NEMA1. : -10 to +40
°
C (14 to 105
°
F)
(not frozen)
Humidity 95% RH or less (non-condensing)
Storage Temperature* -4 to 140
°
F (-20 to +60
°
C)
Location Indoor (free from corrosive gases or dust)
Elevation 3280ft (1000m) or less
Vibration
Up to 9.8m / S
2
(1G) at less than 20Hz, up to 2m / S
2
(0.2G) at less than 20 to 50Hz
* Temperature during shipping (for short period)
# For details, refer to “Reducing motor noise or leakage current (n080)” on
page 68.
Voltage Class 400V 3-phase
Model
CIMR-V7*C
‰‰‰‰
3-phase 40P2 40P4 40P7 41P5 42P2 43P0 43P7 45P5 47P5
Single-phase ––––––