Instruction Manual

136
Protective
Operation
Output is shut
OFF and motor
coasts to a
stop.
EF
(External fault)
Inverter receives an external
fault input from control circuit
terminal.
EF0: External fault reference
through MEMOBUS
communications
EF1: External fault input
command from control
circuit terminal S1
EF2: External fault input
command from control
circuit terminal S2
EF3: External fault input
command from control
circuit terminal S3
EF4: External fault input
command from control
circuit terminal S4
EF5: External fault input
command from control
circuit terminal S5
EF6: External fault input
command from control
circuit terminal S6
EF7: External fault input
command from control
circuit terminal S7
Check the external
circuit (sequence).
CPF-00
Inverter cannot communicate
with the digital operator for 5
sec. or more when power is
turned ON.
Cycle power after
checking the digital
operator is securely
mounted.
If the fault remains,
replace the digital
operator or inverter.
CPF-01
Transmission fault occurred
for 5 sec. or more when
transmission starts with the
digital operator.
Cycle power after
checking the digital
operator is securely
mounted.
If the fault remains,
replace the digital
operator or inverter.
CPF-04
EEPROM fault of inverter
control circuit is detected.
Record all parameter
data and initialize the
parameters. (Refer
to page 32 for
parameter
initialization)
Cycle power.
If the fault remains,
replace the inverter.
Alarm Display
Inverter
Status
Explanation
Causes and
Corrective Actions
Digital
Operator
RUN (Green)
ALARM (Red)