Instruction Manual

125
Unit selection for Frequency Reference Setting/
Display
Parameter and monitor display for which selection of unit function is valid
Function Outline
The frequency reference, output frequency and the numerical data of frequency
reference parameters can be displayed in %, r/min, m/min according to the set value of
parameter n035.
n035 setting
Item Contents
Frequency
reference
parameters
Frequency reference 1 to 8 (Parameters n024 to n031)
Jog frequency reference (Parameters n032)
Frequency reference 9 to 16 (parameters n120 to n127)
Monitor display
Frequency reference display (FREF)
Output frequency display (FOUT)
Frequency reference display (U-01)
Output frequency display (U-02)
Parameter
No.
Parameter Name Description
Initial
Setting
035
Unit Selection for
frequency Reference
Setting / Display
0: in units of 0.01 Hz (less than 100 Hz)
0.1Hz (100 Hz and more)
1: in units of r/min (set the number of motor
poles)
40 to 3999: in any unit
0
Setting Description
0
(Initial value)
Setting unit: 0.01 Hz (less than 100 Hz), 0.1 Hz (100 Hz and more)
Setting range
min{Fmax (n011) x Frequency reference lower limit (n034) to Fmax (n011) Frequency
reference upper limit (n033), 400 Hz}
1
Setting in units of 0.1% : 100.0 % / Fmax (n011)
Setting range
min{Frequency reference lower limit (n034) to Frequency reference upper limit (n033),
(400 Hz ÷ Fmax (n011) 100%}
2 to 39
Setting in units of 1 r/min = 120 x Frequency reference (Hz) ÷ n035
(Set the number of motor poles for n035)
Setting range
min{120 (Fma x (n011) Frequency reference lower limit (n034) ÷ n035~120x
Fmax(n011) x Frequency reference upper limit (n033)) n035, 400Hzx120 P, 9999r/min
Set the display value at 100% of frequency reference (set value of Fmax (n011)) at 1 of
n035.