Instruction Manual
122
The voltage class and maximum applicable motor capacity (whose parameters stored in
the digital operator are read out) is displayed.
[Example] Display the voltage class and maximum applicable motor capacity
for the inverter whose parameters stored in EEPROM inside the digital
operator.
The following shows the explanation of Inverter Capacity Display
Inverter Capacity Display
Explanation Operator display
• Enable the setting of the
parameters n001 to n179.
• Execute Inverter Capacity
Display (vA) by parameter copy
function selection (n176)
• Press DSPL to light [PRGM].
• Press ENTER to display the set
value.
• Change the set value to 4 by
pressing or key.
• Press ENTER.
• Change the parameter No. to
n176 by pressing or key.
• Press ENTER to display the set
value.
• Change the set value to vA by
pressing or key.
• Press ENTER.
• Press DSPL or ENTER.
(Can be a different parameter No.)
( Lit )
(Can be a different set value.)
(Blinks)
(Lit for one second.)
(The parameter is
displayed)
(Lit)
(Lit)
(Lit) (For20P7)*
(The parameter No. is
displayed.)
Voltage class
2 Three-phase 200V
b Single-phase 200V
4 Three-phase 400V
Max. applicable motor capacity
200V class 400V class
0.1 0.1kW -
0.2 0.25kW 0.37kW
0.4 0.55kW 0.55kW
0.7 1.1kW 1.1kW
1.5 1.5kW 1.5kW
2.2 2.2kW 2.2kW
3.0 - 3.0kW
4.0 4.0kW 4.0kW