Instruction Manual

108
Search Operation Power Detection Hold Width (n161)
When the power fluctuation is less than this value, the output voltage is held for 3
seconds. Then the search operation mode is activated. Set the hold width in % of the
power which is currently held.
Power Detection Filter Time Parameter (n162)
Response at load change is improved when this value is small. However, at low
frequency, unstable rotation will result.
Parameter
No.
Name Unit
Setting
Range
Initial
Setting
n161
Search operation
voltage limit
% 0 to 100 0
Parameter
No.
Name Unit
Setting
Range
Initial
Setting
n162
Power detection filter
time parameter
x 4 ms 0 to 255 5 (20 ms)
Parameter
No.
Name Unit
Setting
Range
Initial
Setting
n162
Power detection filter
time parameter
x 4 ms 0 to 255 5 (20 ms)