Datasheet
Compact size - only 27.9 mm deep behind the panel. Reliable “Safe break action.”
• The depth behind the panel is only 27.9 mm for 1 to 4 con tacts, both 
on illuminated and non-illuminated.
• IDEC’s original “Safe break action” ensures that the contacts open 
when the contact block is detached from the operator.
• 1 to 4NC main contacts and 1NO monitor contact
• Push-to-lock, Pull or Turn-to-reset operator
• Direct opening action mechanism (IEC 60947-5-5, 5.2, IEC60947-5-
1, Annex K)
• Safety lock mechanism (IEC 60947-5-5, 6.2)
• Degree of protection IP65 (IEC 60529)
• Silver with gold contacts.
• Two operator sizes: ø29 and ø40 mm
• Dark red (Munsell 5R4/12) or bright red (Munsell 7.5R4.5/14) colors 
are available for the operator of non-illuminated emer gency stop 
switches.
Contact Ratings
NC main contacts (black) /NO monitor contact (blue)
Rated Insulation Voltage (Ui) 300V (illuminated part: 60V)
Rated Thermal Current (Ith) 5A
Rated Operating Voltage (Ue) 30V 125V 250V
Rated Operating Current
Main 
Contacts
AC 
50/60 
Hz
Resistive Load
(AC-12)
– 3A 3A
Inductive Load
(AC-15)
– 1.5A 1.5A
DC
Resistive Load
(DC-12)
2A 0.4A 0.2A
Inductive Load
(DC-13)
1A 0.22A 0.1A
Monitor 
Contacts
AC 
50/60 
Hz
Resistive Load
(AC-12)
– 1.2A 0.6A
Inductive Load
(AC-14)
– 0.6A 0.3A
DC
Resistive Load
(DC-12)
2A 0.4A 0.2A
Inductive Load
(DC-13)
1A 0.22A 0.1A
• Minimum applicable load: 5V AC/DC, 1 mA (reference value) 
(Operating area may vary according to the operating conditions and load 
types.)
• The rated operating currents are measured at resistive/inductive load types 
specied in IEC 60947-5-1.
Illumination Ratings
Rated Voltage Operating Voltage Rated Current
24V AC/DC 24V AC/DC ±10% 11 mA
Specifications
Applicable Standards
IEC60947-5-1, EN60947-5-1
IEC60947-5-5, EN60947-5-5, JIS C8201-5-1, UL991, 
NFPA79, UL508, CSA C22.2 No.14, GB14048.5 
Operating 
Temperature
–25 to +60°C (no freezing)
Illuminated: –25 to +55°C (no freezing)
Storage Temperature –45 to +80°C
Operating Humidity 45 to 85% RH (no condensation)
Operating Force
Push to lock:  10.5N
Pull to reset:  10N
Turn to reset: 0.16 N·m
Minimum Force 
Required for Direct 
Opening Action
60N
Minimum Operator 
Stroke Required for 
Direct Opening Action
4.0 mm
Maximum Operator 
Stroke
4.5 mm
Contact Resistance
50 mΩ maximum (initial value)
Insulation Resistance
100 MΩ minimum (500V DC megger)
Overvoltage Category II
Impulse Withstand 
Voltage
2.5 kV
Pollution Degree 3 (inside LED unit: 2)
Operation Frequency 900 operations/hour
Shock Resistance
Operating extremes:   150 m/s
2
Damage limits:  1000 m/s
2
Vibration Resistance
Operating extremes: 10 to 500 Hz, 
amplitude 0.35 mm acceleration 50 m/s
2
Damage limits:  10 to 500 Hz, 
amplitude 0.35 mm acceleration 50 m/s
2
Mechanical Life 250,000 operations minimum
Electrical Life
100,000 operations min
250,000 operations min (24V AC/DC, 100 mA)
Degree of Protection IP65 (IEC60529)
Short-circuit 
Protection
250V/10A fuse 
(Type aM, IEC60269-1/IEC60269-2)
Conditional 
Short-circuit Current
1000A
Terminal Style Solder terminal, PC board terminal
Recommended 
Tightening Torque 
for Locking Ring
0.88 N·m
Connectable Wire 1.25 mm
2 
maximum (AWG16 maximum)
Soldering Conditions 310 to 350°C, 3 seconds maximum
Weight ø29 mm: 23g, ø40 mm: 28g
Direct Opening Action
www.apem-idec.eu
D-017
ø16 XA Series Emergency Stop Switches (w/Removable Contact Block)
APEM
Switches & 
Pilot Lights
Control Boxes
Emergency 
Stop Switches
Enabling 
Switches
Safety Products
Explosion Proof
Terminal Blocks
Relays & Sockets
Circuit 
Protectors
Power Supplies
LED Illumination
Controllers
Operator 
Interfaces
Sensors
AUTO-ID
Emergency Stop Switches
X6
XA
XW
XN
SEMI
Standards and Specications