Datasheet

3
High level of safety with Safe Break Action.
Mechanical indicator on the operator body shows the
contact status - green when NC contacts are closed - reducing the maintenance work.
•IDEC’soriginal“SafeBreakAction”andReverseEnergyStructure
ensurethesafetyofoperatorandsystem,whentheswitchisdam-
agedduetoexcessiveshocks.
•Themechanicalindicatorontheoperatorbodyshowsthenormal/
latchedstatus(green:normal).Reducesmaintenanceworkand
improvesoperationefficiency.
•Illuminatedmodelalsoavailable(samesizeasnon-illuminated)
•Thedepthbehindthepanelisonly46.4mm(w/terminalcover).
•1to4NCmaincontactsand1or2NOmonitorcontact
•Push-to-lock,PullorTur n-to-resetoperator
•Directopeningactionmechanism
(IEC60947-5-5,5.2,IEC60947-5-1,AnnexK)
•Safetylockmechanism(IEC60947-5-5,6.2)
•Degreeofprotection:IP65(IEC60529)
•Durablegold-platedcontacts
•Finger-safestructure(IP20)
•UL,c-ULlisted.ENcompliant.
•ULNISDcategory
XW Series Emergency Stop Switches (Mechanical Indicator)
ø22
Standards
ApplicableStandards Mark FileNo.orOrganization
UL508
CSAC22.2No.14
UL/c-ULListingFileNo.E68961
IEC60947-5-5
UL991
NFPA79
EN418
ULListingFileNo.E305148
EN60947-5-1
EN60947-5-5(Note)
TÜVSÜD
EUlowvoltagedirective
GB14048.5
CCCNo.2012010305589649
Contact Ratings
(NC main contacts/NO monitor contact)
RatedInsulation
Voltage(Ui)
ScrewTe r minal 250V
RatedThermalCurrent(Ith) 5A
RatedOperatingVoltage(Ue) 30V 125V 250V
RatedOperatingCurrent
Main
Contacts
AC
50/60Hz
ResistiveLoad(AC-12) 5A 3A
InductiveLoad(AC-15) 3A 1.5A
DC
ResistiveLoad(DC-12) 2A 0.4A 0.2A
InductiveLoad(DC-13) 1A 0.22A 0.1A
Monitor
Contacts
AC
50/60Hz
ResistiveLoad(AC-12) 1.2A 0.6A
InductiveLoad(AC-14) 0.6A 0.3A
DC
ResistiveLoad(DC-12) 2A 0.4A 0.2A
InductiveLoad(DC-13) 1A 0.22A 0.1A
•Minimumapplicableload:5VAC/DC,1mA(referencevalue)
(Operatingareadependsontheoperatingconditionsandloadtypes.)
•Theratedoperatingcurrentsaremeasuredatresistive/inductiveloadtypes
specifiedinJISC8201-5-1.
Illumination Ratings
RatedVoltage OperatingVoltage RatedCurrent
24VAC/DC 24VAC/DC±10% 15mA
Note: AnLEDlampisbuiltintothecontactblockandcannotbereplaced.
Specifications
ApplicableStandards
IEC60947-5-5,EN60947-5-5
JISC8201-5-1,UL508,UL991,NFPA79,
CSAC22.2No.14,GB14048.5
OperatingTemperature
Non-illuminated:–25to+60°C(nofreezing)
LEDilluminated:–25to+55°C(nofreezing)
StorageTemperature –45to+80°C(nofreezing)
OperatingHumidity 45to85%RH(nocondensation)
OperatingForce
Pushtolock: 32N
Pulltoreset: 21N
Tur ntoreset:0.27N·m
MinimumForce
RequiredforDirect
OpeningAction
80N
MinimumOperator
StrokeRequiredfor
DirectOpeningAction
4.0mm
MaximumOperator
Stroke
4.5mm
ContactResistance 50mΩmaximum(initialvalue)
InsulationResistance 100MΩminimum(500VDCmegger)
OvervoltageCategory II
ImpulseWithstand
Voltage
2.5kV
PollutionDegree 3
OperationFrequency 900operations/hour
ShockResistance
Operatingextremes:150m/s
2
Damagelimits: 1000m/s
2
VibrationResistance
Operatingextremes:10to500Hz,amplitude0.35mm,
acceleration50m/s
2
Damagelimits:10to500Hz,amplitude0.35mm,
acceleration50m/s
2
MechanicalLife 250,000operationsminimum
ElectricalLife
100,000operationsminimum
250,000operationsminimum
(24VAC/DC,100mA)
DegreeofProtection
Panelfront:IP65(IEC60529)
TerminalProtection:IP20(screwterminal,when
usingXW9Z-VL2MF)
Short-circuitProtection
250V/10Afuse
(TypeaM,IEC60269-1/IEC60269-2)
ConditionalShort-
circuitCurrent
1000A
TerminalStyle M3screwterminal
Recommended
TighteningTorquefor
LockingRing
2.0N·m
ConnectableWire
0.75to1.25mm
2
(AWG18to16)
Recommended
TighteningTorquefor
Ter minalScrew
0.6to1.0N·m
(13/04/04)