Manual
1.3 HG1X Series
Currently models included in the HG1X Series are as follows:
HG1X - 252 and HG1X - 452. HG1X Models take power from the
PLC. Detailed specifications for all the models is given in the
following section.
HG1X-252
Specifications:
Power: 5 VDC+ 5%, 130mA typically from PLC port
Display: 2 lines of 16 characters Backlit LCD
Bezel: IP65 rated Keypad
Keys: 6 User definable keys with tactile feedback
LEDs: 2 LEDs
Memory: 24K Application Memory
Communication: Two RS232 ports, one for connecting to
the PLC and one for programming / serial printing.
Temperature: 0 to 50
o
C
Humidity: 10% to 90% (Non condensing)
Immunity to ESD: Level 3 as per IEC1000-4-2
Immunity to Transients: Level 3 as per IEC1000-4-4
Radiated Susceptibility: Level 3 as per IEC1000-4-3
Emissions: EN55011 CISPR A
System Components:
-
HG1X-252 unit with LCD display and Membrane keypad
- Installation Kit: Gasket, Two Mounting clamps, Two M4
screws, Four hex nuts.
Note: User should order PLC cables and Software separately.
Hardware
In This Chapter. . .
Mounting, Panel Cutouts
Power Requirements
Serial Port
PLC Port
HG1X-452
Specifications:
Power: 5 VDC+ 5%, 140mA typically from PLC port
Display: 4 lines of 20 characters Backlit LCD
Bezel: IP 65 rated Keypad
LEDs: 8 LEDs
Keys: 20 User definable keys with tactile feedback
Memory: 24K Application Memory
Communication: Two RS232 ports, one for connecting to the PLC
and one for programming / serial printing.
Temperature: 0 to 50
o
C
Humidity: 10% to 90% (Non condensing)
Immunity to ESD: Level 3 as per IEC1000-4-2
Immunity to Transients: Level 3 as per IEC1000-4-4
Radiated Susceptibility: Level 3 as per IEC1000-4-3
Emissions: EN55011 CISPR A
System Components:
- HG1X-452 unit with LCD display and Membrane keypad
- Insertable Legends
- Installation Kit: Gasket, Two Mounting clamps, Two M4
screws, Four hex nuts.
Note: User should order PLC cables and Software separately.