User manual

4
RF1V Force Guided Relays / SF1V Relay Sockets
Applicable Crimping Terminals
6.5 min.
4.0 max.
6.3 max.
3.0 min.
Note: Ring tongue terminals cannot be used.
Relay Specifications
Number of Poles 4-pole 6-pole
ContactConguration 2NO-2NC 3NO-1NC 4NO-2NC 5NO-1NC 3NO-3NC
Contact Resistance (initial value) (Note 1) 100mΩmaximum
Contact Material AgSnO
2
(Auashed)
Rated Load (resistive load) 6A 250V AC, 6A 30V DC
Allowable Switching Power (resistive load) 1500 VA, 180W
Allowable Switching Voltage 250V AC, 30V DC
Allowable Switching Current 6A
Minimum Applicable Load (Note 2) 5V DC, 1 mA (reference value)
Power Consumption (approx.) 0.36W 0.5W
Insulation Resistance
1000MΩminimum(500VDCmegger,samemeasurementpositionsasthedielectricstrength)
Dielectric
Strength
Between contact and coil 4000V AC, 1 minute
Between contacts of different poles
2500V AC, 1 minute
Between contacts 7-8 and 9
-
10
2500V AC, 1 minute
Between contacts 7-8 and 11-12
Between contacts 9-10 and 13-14
Between contacts 11-12 and 13-14
4000V AC, 1 min.
Between contacts 3-4 and 5-6
Between contacts 3-4 and 7-8
Between contacts 5-6 and 9-10
4000V AC, 1 min.
Between contacts 3-4 and 5-6
Between contacts 3-4 and 7-8
Between contacts 5-6 and 9-10
Between contacts 7-8 and 9-10
Between contacts of the same pole 1500V AC, 1 minute
Operate Time (at 20°C) 20 ms maximum (at the rated coil voltage, excluding contact bounce time)
Response Time (at 20°C) (Note 3)
8 ms maximum (at the rated coil voltage, excluding contact bounce time)
Release Time (at 20°C) 20 ms maximum (at the rated coil voltage, excluding contact bounce time)
Vibration
Resistance
Operating Extremes 10 to 55 Hz, amplitude 0.75 mm
Damage Limits 10 to 55 Hz, amplitude 0.75 mm
Shock
Resistance
Operating Extremes (half sine-wave pulse: 11 ms)
200 m/s
2
, when mounted on DIN rail mount socket: 150 m/s
2
Damage Limits (half sine-wave pulse: 6 ms) 1000 m/s
2
Electrical Life
250V AC 6A resistive load: 100,000 operations minimum (operating frequency 1200 per hour)
30V DC 6A resistive load: 100,000 operations minimum (operating frequency 1200 per hour)
250V AC 1A resistive load: 500,000 operations minimum (operating frequency 1800 per hour)
30V DC 1A resistive load: 500,000 operations minimum (operating frequency 1800 per hour)
[AC 15] 240V AC 2A inductive load: 100,000 operations minimum
(operating frequency 1200 per hour, cos ø = 0.3)
[DC 13] 24V DC 1A inductive load: 100,000 operations minimum
(operating frequency 1200 per hour, L/R = 48 ms)
Mechanical Life 10 million operations minimum (operating frequency 10,800 operations per hour)
Operating Temperature (Note 4) –40 to +85°C (no freezing)
Operating Humidity 5 to 85%RH (no condensation)
Storage Temperature –40 to +85°C
Operating Frequency (rated load) 1200 operations per hour
Weight (approx.) 20g 23g
Note 1: Measured using 6V DC,1A voltage drop method.
Note 2: Failure rate level P (reference value)
Note 3: Response time is the time until NO contact opens, after the coil voltage is turned off.
Note 4: When using at 70 to 85°C, reduce the switching current by 0.1A/°C.
Socket Specifications
Type SF1V-4-07L SF1V-6-07L SF1V-4-61 SF1V-6-61
Rated Current 6A
Rated Voltage 250V AC/DC
Insulation Resistance
1000MΩminimum
(500V DC megger, between terminals)
Dielectric Strength 2500V AC, 1 minute (between terminals)
Screw Terminal Style M3 slotted Phillips screw
Applicable Wire
0.7 to
1.65 mm
2
(18 AWG to 14 AWG)
Recommended Screw
Tightening Torque
0.5 to 0.8 N·m
Terminal Strength Wire tensile strength: 50N min.
Vibration Resistance
Damage limits: 10 to 55 Hz, amplitude 0.75 mm
Resonance: 10 to 55 Hz, amplitude 0.75 mm
Shock Resistance 1000 m/s
2
Operating Temperature
(Note)
40 to
+85°C (no freezing)
Operating Humidity 5 to 85% RH (no condensation)
Storage Humidity
40 to +85°C
Degree of Protection
IP20
(nger-safescrewterminals)
Weight (approx.) 40g 55g 9g 10g
Note: When using at 70 to 85°C, reduce the switching current by 0.1A/°C.
(090319)