Datasheet

PS6R Switching Power Supplies
Accessories (For use with PS6R)
Part No.
DC-DC Converter Unit (Note 5)
Expansion
Terminal Unit
PS9Z-6RM1 PS9Z-6RM2 PS9Z-6RM3 PS9Z-6RM4 PS9Z-6RM5 PS9Z-6RM6 PS9Z-6RS1
Output Capacity 10W max. 12W max. 10W max. 12W max. 11W max. 12W max.
Output
Rated Voltage/Current 5V/2A 12V/1A ±5V/1A ±15V/0.4A
5V/1A, 12V/0.5A
±12V/0.5A
24V/10A max.
(Note 1)
Adjustable Voltage
Range
Not available
Voltage Accuracy ±5% max.
Start Time (Note 6) 200 ms max. (at rated output)
Regulation
Input Fluctuation 0.5% max.
Load Fluctuation 1.0% max.
Temperature
Change
0.05%/max. (–10 to +60°C)
Ripple (including
noise)
100mV max. 150mV max. 100mV max. 150mV max.
100mV max.,
150mV max.
150mV max.
Supple-
mentary
Functions
Overcurrent Protection 105% (auto reset)
Overvoltage Protection Output off at 120% (Note 2)
Operating Temperature –10 to +70°C (no freezing) (Note 3)
Operating Humidity 20 to 90%RH (no condensation)
Storage Temperature –25 to +75°C (no freezing)
Storage Humidity 20 to 90% RH (no condensation)
Vibration Resistance 10 to 55 Hz, amplitude 0.375 mm, 2 hours each in 3 axes, 6 directions (in combination with PS6R-F24/G24/J24)
Shock Resistance
300 m/s
2
(150 m/s
2
when using a PS9Z-6R1F panel mounting bracket),
3 times each in 6 directions (in combination with PS6R-F24/G24/J24)
EMC
EMI EN61204-3 (Class B) (in combination with PS6R-F24/G24/J24) (Note 4)
EMS EN61204-3 (industrial) (in combination with PS6R-F24/G24/J24) (Note 4)
Safety Standards UL508 (Listing), CSA C22.2 No.107.1, IEC/EN60950-1, EN50178 (in combination with PS6R-F24/G24/J24)
Degree of Protection IP20 (IEC 60529)
Weight (approx.) 90g 30g
Terminal Screw M3.5
Note 1: Ensure that the current does not exceed the rated current of the PS6R.
Note 2: Repair is needed when output drops due to overvoltage protection. Contact IDEC.
Note 3: For output derating curves and operating temperature approved by safety standards, see page 7.
Note 4: When using PS6R-F24/G24 with PS9Z-6RM3/6RM4/6RM6, coil each output lines of PS9Z-* around a ferrite core for one turn.
Note 5: DC-DC converter unit is non-isolated and cannot be used when insulation against PS6R output is required.
Note 6: Because each output has different start time on multi-output models, make sure of the correct operation before installation.
6
(13/11/08)