Manual

WEB SERVER CPU MODULE USERS MANUAL FC9Y-B1278 3-11
3: INSTALLATION AND WIRING
Input Wiring
Output Wiring
Separate the input wiring from the output line, power line, and motor line.
Use proper wires for input wiring.
All-in-one type CPU modules: UL1015 AWG22 or UL1007 AWG18
Slim type CPU and I/O modules: UL1015 AWG22
Caution
If output relays or transistors in the Web Server CPU or output modules should fail, outputs may remain on
or off. For output signals which may cause heavy accidents, provide a monitor circuit outside the Web
server CPU module.
Connect a fuse to the output module, selecting a fuse appropriate for the load.
Use proper wires for output wiring.
All-in-one type CPU modules: UL1015 AWG22 or UL1007 AWG18
Slim type CPU and I/O modules: UL1015 AWG22
When equipment containing the Web server CPU module is intended for use in European countries, insert
an IEC 60127-approved fuse to each output of every module for protection against overload or short-
circuit. This is required when equipment containing the Web server CPU module is destined for Europe.
Caution