Manual

7: USING WINDLDR
MICROSMART AS-INTERFACE MASTER MODULE USERS MANUAL 7-3
Configuration
Before commissioning the AS-Interface master module, conguration must be done using either WindLDR or the pushbut-
tons on the front of the AS-Interface master module. This section describes the method of conguration using WindLDR.
Conguration is the procedure to store the following information to the AS-Interface master module EEPROM.
A list of slave addresses to be used
Conguration data to specify slave types, or identication codes (ID, I/O, ID2, ID1)
Parameters (P3, P2, P1, P0) to designate the slave operation at power-up
WindLDR provides two options for conguration: auto conguration to execute automatic conguration and manual con-
guration to execute conguration according to the data selected by the user.
Auto Configuration
Auto conguration stores the current slave conguration data (LDS, CDI, PI) to the AS-Interface master module
EEPROM (LPS, PCD, PP). To execute auto conguration, press Auto Conguration in the Congure AS-Interface Mas-
ter dialog box. Auto conguration takes approximately 1 minute, and has the same effect as the conguration using the
pushbuttons on the AS-Interface master module.
Manual Configuration
Manual conguration is the procedure
to write the LPS, PCD, and PP desig-
nated on WindLDR to the AS-Interface
master module EEPROM. LPS is auto-
matically generated by WindLDR based
on the value for PCD.
To change PCD and PP, use the Congure Slave dialog box. Set the
PCD of each slave to the same value as its CDI. If the PCD is differ-
ent from the CDI for a slave, then that slave does not function cor-
rectly. Set FFFFh to the PCD of vacant slave numbers.
After entering a PCD value and selecting parameter statuses, click
OK. At this point, the conguration data are not stored to the AS-
Interface master module EEPROM. To store the changes, click Manual Conguration on the Congure AS-Interface
Master dialog box. The screen display of the Congure AS-Interface Master dialog box can be updated using Refresh.
If you save the conguration data to a le, you can open the le to congure other AS-Interface master modules using the
same data. To save and open the conguration le, click File Save or File Open.
If the conguration command is not processed correctly, the error message “AS-Interface Master Error” and an error code
will appear. See page 7-5.
If the error message “Conguration failure. Conrm the slave setup, and perform conguration again.” is shown, and the
FLT LED is on, then remove the cause of the error, referring to page 4-7, and repeat conguration.
The conguration cannot be done in the following cases.
Slave Configuration Data AS-Interface Master Module EEPROM
List of detected slaves (LDS)
Configuration data image (CDI)
Parameter image (PI)
List of projected slaves (LPS)
Permanent configuration data (PCD)
Permanent parameter (PP)
Error Code Description
1
An error was found on the expansion I/O bus.
2
While the AS-Interface master module was in offline mode, attempt was made to execute auto
configuration or manual configuration.
7
While slave address 0 existed on the bus, attempt was made to execute auto configuration or
manual configuration.
The AS-Interface master module is in local mode.
Configuration
Permanent
Parameter
(PP)
PCD LPS
FFFFh 0
Other values 1