4: OPERATION BASICS
MICROSMART AS-INTERFACE MASTER MODULE USERS MANUAL 4-5
Configuration Using WindLDR
Slave conguration can be set using
WindLDR in two ways; using the Auto Conguration or Manual Conguration but-
ton on the Congure AS-Interface Master dialog box.
1. Click the A
uto Conguration button to store the conguration information (LDS, CDI, PI) of the connected slaves to
the EEPROM (LPS, PCD, PP) in the AS-Interface master module. For details, see page 7-3.
The auto conguration automatically stores the information of slaves found on the AS-Interface bus to the EEPROM in the
master module, and this completes conguration. Another method of conguration is manual conguration as follows.
2. Click the PCD value “FFFF” of slave address 01 to open the Congure Slave 01A dialog box.
3. Enter the same value as CDI “07F7” to the PCD eld. (Set FFFF to PCD values of all unused slaves.)
4. Select initial settings of parameters 0 through 3, if required.
5. Click the M
anual Conguration button to store the selected PCD and parameter values to the master module.
6. Check that the blue shade appears at slave address 01. Now, conguration is complete.
Yellow Shade
Blue Shade