Datasheet

19
HS6E Subminiture Interlock Switches with Solenoid
Standard – Solenoid Lock
Interlock Switch Status
Status 1 Status 2 Status 3 Status 4
Unlocking using
Manual Unlock Key
• Door closed
• Machine ready to
operate
• Solenoid
energized
• Door closed
• Machine cannot
be operated
• Solenoid
de-energized
• Door open
• Machine cannot
be operated
• Solenoid
de-energized
• Door open
• Machine cannot
be operated
• Solenoid
energized
• Door closed
• Machine cannot
be operated
• Solenoid
de-energized
Door Status
Manually
Unlocked
LOCK
UNLOCK
Circuit Diagram (Example: HS6E-N7Y)
22
3433
21
A1
(–)
A2
(+)
53
4112
54
4211
21
33 34
22
11 42
54
12 41
53
(+)
A2
(–)
A1
22
3433
21
A1
(–)
A2
(+)
53
4112
54
4211
A1
(–)
A2
(+)
53
4112
54
4211
22
3433
21
Door
Closed (locked) Closed (unlocked) Open Open Closed (unlocked)
Model and Circuit Diagram
HS6E-L7Y
Main Circuit 11-42
ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Door Monitor Circuit
(door closed) 21-22
ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Door Monitor Circuit
(door closed) 31-32
ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Lock Monitor Circuit
(unlocked) 53-54
OFF (open) ON (closed) ON (closed) ON (closed) ON (closed)
HS6E-M7Y
Main Circuit 11-42
ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Door Monitor Circuit
(door closed) 21-22
ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Door Monitor Circuit
(door closed) 31-32
ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Lock Monitor Circuit
(locked) 51-52
ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
HS6E-N7Y
Main Circuit 11-42
ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Door Monitor Circuit
(door closed) 21-22
ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Door Monitor Circuit
(door open) 33-34
OFF (open) OFF (open) ON (closed) ON (closed) OFF (open)
Lock Monitor Circuit
(unlocked) 53-54
OFF (open) ON (closed) ON (closed) ON (closed) ON (closed)
HS6E-P7Y
Main Circuit 11-42
ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Door Monitor Circuit
(door closed) 21-22
ON (closed) ON (closed) OFF (open) OFF (open) ON (closed)
Door Monitor Circuit
(door open) 33-34
OFF (open) OFF (open) ON (closed) ON (closed) OFF (open)
Lock Monitor Circuit
(locked) 51-52
ON (closed) OFF (open) OFF (open) OFF (open) OFF (open)
Solenoid Power A1-A2 (all model)
ON (energized) OFF (de-energized) OFF (de-energized)
ON (energized)
(Note 2)
OFF (de-energized)
to ON (re-energized)
(Note 1) (Note 2)
Main circuit: Connected to the machine drive control circuit, sending the interlock signals of the protective door.
Monitor circuit: Sends the monitoring signals of open/closed and lock/unlocked statuses of the protective door.
Note 1: Do not attempt manual unlocking while the solenoid is energized.
Note 2: Do not energize the solenoid for a long period of time while the door is open or while the door is unlocked manually using the manual unlock key.
Operation Characteristics (reference)
Monitor Circuit:
Monitor Circuit:
Monitor Circuit:
Monitor Circuit:
Monitor Circuit:
Monitor Circuit:
Monitor Circuit:
Monitor Circuit:
A1A2
(+) (–)
22
11
21
12 4241
5453
41 421211
11 12 4241
41 421211
21 22
51 52
51 52
Main Circuit:
Main Circuit:
Main Circuit:
Main Circuit:
33
34
31 32
53 54
3433
2221
3231
2221
Door
Monitor
Lock
Monitor
(When inserted) (When ON)
28.2
5.8
1.9
0.80
5.5
Door Monitor Circuit (door closed, NC)
Lock Monitor Circuit (locked, NC)
Door Monitor Circuit (door open, NO)
Main Circuit
Lock Monitor Circuit (unlocked, NO)
: Contacts ON (closed)
: Contacts OFF (open)
(Actuator Insertion Position)
(Locked Position)
(stroke in mm)
•The characteristics shown in the chart above are of the HS9Z-A61, -A62, -A65, and -A66 actuators.
For the HS9Z-A62S actuator, subtract 0.6 mm.
•The characteristics show the contact status when the actuator enters an entry slot of an interlock switch.
HS6E