HS5L Interlock Switches with Solenoid
Applicable Cable Glands
Use a cable gland with IP67 protection degree.
Applicable Cable Gland Dimensions
9mm max.
M20
30mm max.
When Using Flexible Conduits (example)
Flexible conduit example: VF-03 (Nihon Flex)
Conduit Port Size Plastic Cable Gland Metal Cable Gland
M20 RLC-103EC20 (Nihon Flex)
When Using Multi-core Cables (example)
Flexible conduit example: VF-03 (Nihon Flex)
Conduit Port Size Plastic Cable Gland Metal Cable Gland
M20
ST-M20X1.5
(Manufacturer: LAPP)
(Distributor: K-MECS)
ALS-EC20
(Nihon Flex)
Different cable glands are used depending on the cable sheath
outside diameter. When purchasing a cable gland, conrm that the
cable gland is applicable to the cable sheath outside diameter.
When using ST-M20X1.5, use with gasket below:
GPM20 (Manufacturer: LAPP Distributor: K.MECS)
Lead-in Wire Length and Wiring Examples
L1
8 to 9mm
Connector
Interlock switch
Part No. Cable Orientation Cable Length (L1)
HS5L-4M-G
HS5L-4LM-G
Straight 30 to 35mm
HS5L-4SM-G
HS5L-4LSM-G
Side (right or left)
50 to 55mm
40 to 45mm
Terminal wiring diagram
4-Contact
2-Contact
31/33/
51/53
32/34/
52/54
21/23/
63
22/24/
64
21/23/
41/43
22/24/
42/44
11/13/
51/53
12/14
52/54
Notes:
Circuit No. A, B, C, D, F, G, J: 12-41 are connected using a jumper.
Circuit No. DD: 12-41, 22-51 are connected using a jumper.
When connecting the NC contact (11-12, 21-22) of door monitor
circuit and NC contacts (41-42, 51-52) of the lock monitor circuit
in a series as an input to a safety circuit, connect 12-41 or 22-51.
Cautions for Wiring
Use the following applicable wiring. Stranded wire or solid wire
(1 wire): 0.3 to 1.5mm
2
(AWG22 to AWG16)
Make sure to strip the wire insulation 8 to 9mm from the end. If the
strip length is too short, the wire may fall out. If the strip length is
too long, it may short circuit with other wires.
Twist the wires and make sure that there are no wire whiskers.
When using stranded wires without ferrules, make sure that the
core wires have not been loosened.
For wiring, use screwdrivers as
shown in the right. (The shape
of the tip of the screwdriver is in
accordance with DIN5264)
The inserting port of the wire and
screwdriver, and direction of the tip is
as shown in the diagram below.
Screwdriver port
and direction of the
screwdriver tip.
Wire port
When using ferrules for stranded wires, use the ferrule listed in
the following table.
Compatible Wire Model No. Manufacturer
0.34mm
2
AWG22 AI0.34-6TQ
Phoenix Contact
0.5mm
2
AWG20 AI0.5-6WH
0.75mm
2
AWG18 AI0.75-6GY
1mm
2
AWG18 AI1-6RD
0.5mm
2
AWG20 TE0.5-8
NICHIFU Co., Ltd.0.75mm
2
AWG18 TE0.75-8
1mm
2
AWG18 TE1.0-8
Wire connection method
1. Insert the screwdriver into the square-
shaped port from a slightly slanted
angle as shown, until the screw-driver
tip touches the bottom of the spring.
Make sure that the direction of the blade
edge is correct.
2. Push in the screwdriver until it touches
the bottom of the port. The wire port is
opened, and the screwdriver is held in
place. The screwdriver will not come off
even if you release your hand.
3. While the screwdriver is retained in
the port, insert the wire or ferrule
into the round-shaped wire port.
4. Pull out the screwdriver.
The connection is now complete.
Safety Precautions
When using wires with insulation diameter of ø2.0mm or less, do
not insert the wire too deeply where the insulation inserts into
the spring clamp opening. Make sure that the wire insulation is
stripped 8 to 9mm and the wire is inserted to the bottom.
8 to 9mm
Incorrect Correct
Wire inserted to
the bottom
Insulation inserted
too deep
0.4
7º to 13
ø2.5
2.5
If there is a need to insert the
screwdriver while holding the
interlock switch with hands,
be careful not to injure your
ngers with the tip of the
screwdriver.
Connect one wire to one
wiring port.
(According to IEC 60204 (JIS 9960-1) 13.1.1 General Requirement)
8 to 9mm
Incorrect Correct
Wire inserted to
the bottom
Insulation inserted
too deep
0.4
7º to 13
ø2.5
2.5