User guide
Chapter 2
532
External Device Setup Manual
21.4 Environment Settings
The communication port settings for VB/VH series and MICRO/I host port are as follows.
21.4.1 VB/VH Series (Communication Port for Programming Tool)
21.4.2 VB/VH Series (VB-485A, VB-232 or VB-485)
21.4.3 VB/VH Series (VB-CADP)
Refer to the VB/VH Series user’s manual for details of communication settings.
Items Details
Interface RS232C
Baud Rate [bps] Use the same settings as
for the MICRO/I.
19200 (fixed)
Data Bits 7 (fixed)
Parity Even
Stop Bits 1 (fixed)
Flow Control None
Station Number 0 (fixed)
Items Details
Interface RS232C, RS485 4-wire
Baud Rate [bps] Use the same settings as
for the MICRO/I.
1200, 2400, 4800, 9600, 19200 or 38400
Data Bits 7
Parity Even
Stop Bits 1
Flow Control None
Station Number 0 - 255(DEC)
Items Details
Port CP2 CP3
Interface RS232C, RS485 RS485
Baud Rate [bps] Use the same settings as
for the MICRO/I.
1200, 2400, 4800, 9600, 19200 or 38400 19200
Data Bits 7 7
Parity Even Even
Stop Bits 1 1
Flow Control None None
Station Number 0 - 255(DEC) 0 - 99(DEC)