User guide

Chapter 2
234
External Device Setup Manual
5.4 Environment Settings
5.4.1 S7-200
The communication port settings for S7-200 and MICRO/I host port are as follows.
Items Details
PLC Address 1 to 126(Dec) (0 to 7e (Hex))
Set the value to same value as ADDRESS (PLC) in WindO/I-NV2.
Highest Address (Highest Station
Address)
1 to 126(Dec) (0 to 7e(Hex))
Set the value to same value as HSA in WindO/I-NV2.
Baud Rate (bps) 9600 or 19200
Set the value to same value as Baud Rate in WindO/I-NV2.
HG Address 0 to 7e (Hex) (0 to 126(Dec))
Set the value as ADDRESS (HG) in WindO/I-NV2.
Data Bits 8 (fixed)
Set the value in WindO/I-NV2.
Parity EVEN (fixed)
Set the value in WindO/I-NV2.
Stop Bits 1 (fixed)
Set the value in WindO/I-NV2.
- Set the communication port that communicates with MICRO/I to PPI/Slave mode. Please make sure to set SMB30 or
SMB130 values to 0 in order to select proper communication port settings. Refer to the manual of S7-200 for details.
- We checked the following problems in some versions of S7-200.
When S7-200 is set as the master and the address of S7-200 is the same as HSA, token path does not work correctly.
This problem can be solved by setting HSA as a larger value than Address actually used.
This problem does not occur when one MICRO/I is connected to one S7-200 PLC.