Connection to a PLC
External Device Setup Manual
4.4 Environment Settings
Allowed communication settings for MicroLogix, SLC 500, PLC-5, ControlLogix and CompactLogix are as follows.
4.4.1 MicroLogix, SLC 500 (Full Duplex)
Item Setting
Baud Rate (bps)
*1
*2
*1. Select using RSLogix software (set Chan0 to System of Controller-Channel Configuration).
*2. The setting for this item must match the setting on the MICRO/I Series unit.
1200, 2400, 4800, 9600 or 19200
Data Bits
*2
8 (fixed)
Parity
*1
*2
None or Even
Stop Bits
*1
*2
1
Flow Control Hardware or None
Serial Interface RS232C
Driver
*1
DF1 Full-Duplex
*3
*3. Be certain to select as indicated.
Control Line
*1
No Handshaking
*3
Error Detection
*1
CRC
*3
Embedded Response
*1
Auto Detect
Duplicate Packet Detect
*1
Enable
Node Address
*1
*2
*4
*4. Be certain to select as indicated.Select the MICRO/I Node Address using the Node Address (MICRO/I) under Project Settings in WindO/
I-NV2 software.
0 to 254 (decimal)