User guide

Chapter 2
154
External Device Setup Manual
3.4.5 SYSMAC-CS1 Series (Communication Board) Settings
Write the Communication Board setting items for the System Settings Area using a peripheral tool (such as Proconn).
3.4.6 CPU Direct Settings (CPM1/CPM1A/CPM2A)
Connect via CPM-CIF01 (RS232C)/CPM 1-CIF11 (RS422).
The communication settings are fixed. Refer to the PLC manual for details.
System Settings Area Item Setting
Port 1 Port 2
DM32000 DM32010
Optional/Initial Setting
*1
(*1)
*1. Initial settings
Baud Rate: 9600bps
Data Bits:7bits
Stop Bits:2bits
Parity: Even
Set to 1 for Optional Setting.
Serial Communication mode Set to PLC Link.
Data Bits Use the same settings as for the MICRO/I.
Stop Bits
Parity
DM32001 DM32011 Port Communication Speed Use the same settings as for the MICRO/I.
DM32002 DM32012 Transmission Delay setting 0 for default (0mses)
Delay time setting
DM32003 DM32013 CTS control Set to 0 for no
Unit No. Use the same settings as for the MICRO/I.
- Set the DIP switch 4 line.
- Set the DIP switch to ON to turn the termination resistor setting ON.
Item Setting
RS232C
Baud Rate 9600 bps
Data Bits 7 bits
Stop Bits 2 bits
Parity Even