User guide

Chapter 2
152
External Device Setup Manual
3.4.3 CPU Unit RS232C Link I/F Settings (SYSMAC-CS1 Series)
Write the RS232C I/F setting items for the System Settings Area using a peripheral tool (such as Proconn).
Refer to the PLC manual for details.
For the SYSMAC-CS1 Series, set switch number 5 on the CPU Unit setting switch to OFF to enable you to make your own
communication settings.
Channel Item Setting
160
Optional/Initial Setting
*1
*1. Initial settings
Baud Rate: 9600 bps
Data Bits: 7 bits
Stop Bits: 2 bits
Parity: Even
Set to 1 for Optional Setting.
Serial Communication mode Set to PLC Link.
Data Bits Use the same settings as for the MICRO/I.
Stop Bits
Parity
161 Port Communication Speed Use the same settings as for the MICRO/I.
162 In the case of No Protocol Mode Do not set.
163 Unit No. Set to the same as the MICRO/I PLC Link Station Number.
164 In the case of No Protocol Mode Do not set.