User guide

Chapter 2
98
External Device Setup Manual
2. PLC Settings
Refer to the Q Corresponding Ethernet Interface Module Users Manual or Q Corresponding Ethernet Interface Module
Users Manual for detail.
Item setting notes
Network parameter Network type Ethernet
*1
*1. The setting of the above-mentioned is recommended.
Starting I/O No. 0020
*2
*2. Set it according to the environment.
Network No. 1
*2
Total stations - -
Group No. 0
*2
Station No. 1
*2
Mode On line
*1
Operation Setting Communication data code Binary code
*1
Initial Timing Always wait for OPEN
*1
IP Address Input format Decimal
*2
IP address Set IP address of PLC
*2
Send frame setting Ethernet
*1
Enable Write at RUN time Check mark (enable)
*1
TCP Existence confirmation setting Use the Keep Alive
*1
Open Setting Protocol TCP/IP
*1
Open system Impassive open
*1
Fixed buffer Send
*1
Fixed buffer communication Procedure exist
*1
Pairing open No pairs
*1
Existence confirmation No confirm
*1
Local station Port No. Set an arbitrary port number
*2
*3
*3. MICRO/I is set by the decimal number though PLC is set by the hexadecimal number.
Destination IP address - -
Dest. Port No. - -