Manual

WindO/I-NV2 User’s Manual 15-15
3 Operation Log Settings Dialog Box
15
Operation Log Function
Batch
Select this check box to batch output all the sampled data to the memory card.
All the data is saved on the memory card when the trigger device changes from 0 to 1. If a file with the same name
already exists on the memory card, that file is overwritten. The maximum amount of output data is the amount
configured by the data storage area.
*1 Advanced mode only
Output stops if there is insufficient free space on the memory card. Memory card error information is stored
in HG special register LSD42.
Trigger Device: Specifies the bit device that triggers batch output. For the device address configuration
procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-67.
Data is output to file when the trigger device changes from 0 to 1.
File Name: Enter the file name for the output data or shows the file name.
The default is “OPLOGO.CSV”.
To change the file name, enter a new file name. The maximum number is 120 characters
(including the extension).
Specify File Name by Value of Device
*1
:
Select this check box to specify the name of the file for the output data with the value of the
device configured by (File Name Device).
(File Name Device): Specifies the word device that is the source of the data to use as
the file name. The file name is set by reading the values
sequentially from the starting device specified with the file name
device and handling those values as character data up to the
character before NULL (00).
The maximum number of devices is 40 (80 single-byte characters).
You can only specify an internal device. For the device address
configuration procedure, refer to Chapter 2 “5.1 Device Address
Settings” on page 2-67.
Example: When the device specified by (File Name Device) is LDR100 and the text to set is
"IDEC":
The file name at this time becomes "IDEC.CSV".
LDR100
LDR101
LDR102
(File Name Device)
4844
(Hex)
4543
(Hex)
‘ I ’
‘D’
‘E’ ‘C’
0000
(Hex)
(NULL)