Manual

WindO/I-NV2 User’s Manual 13-29
3 Alarm Log Settings Dialog Box
13
Alarm Log Function
Beep Tab
The Beep tab is used to configure whether or not the MICRO/I’s internal buzzer operates.
Beep when Alarm occurs
Select this check box to sound a beep when an alarm has occurred.
Stop Beep
*1
Select the check box for the items that will trigger the beep to stop.
*1 Advanced mode only
*2 The first alarm that has occurred in a state where no alarms are active
HG3G
HG2G-5FHG2G-5SHG2G-S
HG4G HG1F HG2F HG2S HG3F HG4F
Beep only First Alarm
*1
: Select this check box to sound a beep only when the first alarm
*2
has
occurred.
No beeps will sound when another alarm is already active. Clear this
check box to sound a beep each time an alarm occurs.
Stop when touch everywhere on the screen: The beep stops when you touch anywhere on the screen.
Stop when press CHECK/All Chk. button: The beep stops when you touch the key buttons CHECK or All Chk. on
the Alarm Log Display.
Stop when all Alarms are recovered: The beep stops when all the alarms are recovered from.
While the beep is sounding, System Area 1 address + 1 bit 6 is 1.
To stop the beep when an alarm has occurred, use the following methods.
- Press the key button Stop Beep
- When a condition selected with the Stop Beep check boxes is satisfied
- Set System Area 1 address + 1 bit 6 to 0.
However, when 1 is written to System Area 1 address + 1 bit 6 for a reason other than the occurrence of
an alarm, the beep does not stop until 0 is written.