Manual
5 HG3F/4F
34-62 WindO/I-NV2 User’s Manual
5.5 Specifications
■ Applicable Standards
■ Environmental Specifications
■ Electrical Specifications
■ Construction Specifications
Safety Standard UL508, UL1604, CSA C22.2 No.213 (c-UL)
EMC Standard IEC/EN 61000-6-4, IEC/EN 61131-2
Type No. HG3F HG4F
Operating Ambient Temperature 0 to 50°C 0 to 45°C
Operating Relative Humidity 20 to 85% RH (no condensation)
Storage Ambient Temperature -20 to +60°C
Storage Relative Humidity 20 to 85% RH (no condensation)
Altitude (Operation) 0 to 2000m
Pollution Degree 2
Corrosion Immunity Free from corrosive gases
Rated Operating Voltage 24V DC
Power Consumption 25W maximum
Power Voltage Range 19.2V DC to 28.8V DC
Allowable Momentary Power
Interruption
10 ms maximum
Inrush Current 15A maximum (cold start)
Dielectric Strength AC1500V, 10mA, 1 minute (between power and earth terminals)
Insulation Resistance 10 MΩ minimum (500V DC megger) (between power and earth terminals)
Vibration Resistance
10 to 55 Hz, 9.8 m/s
2
[2 hours each in 3 axes] (IEC60068-2-6)
Shock Resistance
147 m/s
2
, 11 ms
[5 shocks each in 3 axes] (IEC60062-2-27)