3 HG1F
34-40 WindO/I-NV2 User’s Manual
■ Performance Specifications
■ EMC Specifications
*1 The backlight life refers to the time until the surface brightness reduces to a half after using continuously at room
temperatures.
*2 Not a guarantee in all usage environments with oil materials.
Display
LCD Type STN monochrome LCD
Display Colors 2 Colors(16 Tones)
Effective Display Area
[mm]
115.0(W) × 39.0(H)
Display Resolution 300 (W) × 100 (H) pixels
Brightness of LCD only
500 [cd/m
2
]
Contrast Adjustment 32 levels
Backlight Cold-cathode tube
Backlight Life
*1
50,000 hours minimum
Touch
Panel
Switch Type Analog Resistive Film
Operating Force 0.2 to 0.8 N
Multiple Operations Impossible
Life 1,000,000 operations
User Memory 1MB
Backup Battery
CR2032 lithium primary battery
Guarantee Period: 1 Year (at 25°C)
Recommended Replacement Span: Every 4 Years (at 25°C)
Backup Data Calendar, Log Data, Keep Internal relay/resister
Buzzer output Single tone (tone length is adjustable)
Degree of Protection
IP65 (operator)
TYPE 13
*2
Weight (approx.) 280g
Radiated Emission
Class A : 10m
40dBµV/m quasi-peak (30M to 230MHz)
47dBµV/m quasi-peak (230M to 1GHz)
Electrostatic Discharge
Contact : ±6kV
Air : ±8kV
Electromagnetic Field
10V/m (80 to 1000 MHz, 1.4 to 2.0 GHz)
80% AM (1kHz)
Fast Transient Burst
Power : ±2kV
Communication cable : ±1kV
Surge Immunity
±500V (between +24V-0V)
±1kV (between +24V-FE, 0V-FE)
Conducted Radio
Frequency Immunity
3V (Power, Communication cable)
(150kHz to 80MHz)
80% AM (1kHz)