Manual
5 User Communication
3-30 WindO/I-NV2 User’s Manual
■ Status Device
Specify the destination word device for the transmitted or received data size and error information. Error information 
and command data size is stored at the beginning of the configured device address. When data transmission or 
receiving has not successfully completed, the value of each bit changes to 1. The bits of the Status Device changes to 
0 when the trigger condition is satisfied and they are not changed to 0 automatically. When Always Enabled is 
selected in Trigger Condition of receive command, the value of the Status Device is kept as long as a Clear 
command is not executed.
You can only specify an internal device.
Click   to display the Device Address Settings dialog box. For the device address configuration procedure, refer to 
Chapter 2 “5.1 Device Address Settings” on page 2-67.
Example: When LDR110 is configured as Status Device
When TXD is selected as Command Type:
Address
Bit Function Cause Solution
+0
0 BCC Error
• The Calculation Start Position and Calculation 
End Position are not stored in 1 frame.
• The Calculation End Position is set before 
Calculation Start Position.
Change the Calculation 
Start Position and 
Calculation End Position 
settings.
• When Calculation Type is 
Modbus ASCII 
(LCR)
, the data size from Calculation Start 
Position to Calculation End Position is odd 
bytes.
• The data contains data other than ASCII (30h 
to 39h, 41h to 46h) data.
Change the Calculation 
Start Position and 
Calculation End Position 
settings and the 
transmission data.
1, 2
Reserved
3
Registering Constant 
Data Error
When data type is Registering Constant 
(Character) or Registering Constant 
(Hexadecimal), the value of the Index Device 
does not match the Index No. of the registered 
Registering Constant.
Change the data stored in 
the Index Device.
4
Reserved
5
Use Reference Device 
Data Error
When data type is Device and the Use 
Reference check box is selected, the device 
address in which the value of the Reference 
Device is stored as offset has exceeded the valid 
range.
Change the value stored in 
the Reference Device.
6
Device Data Variable 
Specification Error
When data type is Device, the Variable check 
box is selected and Device is selected, the 
value of device is negative or exceeds the 
setting (number of bytes x number of words).
Change the value of device 
to a positive value or to a 
value that does not exceed 
the setting (number of bytes 
x number of words).
7
Transmission 
Command Abandon 
Error
When transmitting data after the Trigger 
Condition is satisfied, the command with the 
same Command No. was transmitting data or 
transmission (transmission is not completed).
Increase the time interval 
for starting transmission.
8 to 15
Reserved
Address
Function Description
+1 Transmission Data Size (bytes) Stores the size of transmission data.
LDR110
LDR111
Error information and time out information
Transmitted or received data size (bytes)
(Starting address) +0
+1
When the Error Information bit changes to 1, data is not transmitted, and the Transmission Completed 
Device does not change to 1.