Manual

WindO/I-NV2 User’s Manual 29-5
2 Digital I/O Units
29
Expansion Modules
Writing to an external output
Output refresh
Outputs are refreshed every 10 ms independent of the screen scan.
HG Digital Output (LEY) are reflected in the digital I/O unit.
Output delay
The min-to-max delay time for HG Digital Output (LEY) to fire from the digital I/O unit is 1 ms to 11 ms. This does not
affect the display processing
Control processing
Digital I/O unit output
Output
refresh
LEY
LEY
Y
10 ms
Output
refresh
10 ms
Output
refresh
10 ms
Scan time
Output
delay
Output
delay
Start of scan
Display
processing
1 scan
External output
Y
External output
HG Digital
Output
HG Digital
Output
End of scan
The maximum output delay is 11 ms, which is the operating time of
the output refresh.
LEY
Y
Output
refresh
Output delay
(maximum)
HG Digital
Output
External output