Owner manual
LOGIC 
5-44 
Functions (Logic 11C) 
●Safety inputs: X0 to X13 (T4 to T13) 
Safety inputs are used to diagnose the status of connected safety devices, such as emergency stop 
switches, and interlock switches. 
Intended inputs 
(Terminal names) 
Function 
Function name  Dual channel safety input 
Symbol 
Dual Channel Safety
Description of operation  This function diagnoses the status of 
connected safety devices. This function 
diagnoses the time interval of status 
transition between each input of 
duplicated inputs (0.1s). The function 
does not use drive terminals (T0 to T3). 
Safety input 1 
(X0, X1) 
Safety input 2 
(X2, X3) 
Detail information  Logic functions (5-317) 
Intended inputs 
(Terminal names) 
Function 
Function name  Dual channel direct opening input 
Symbol 
Dual Channel
Direct Opening
Description of operation  This function diagnoses the status of 
connected safety devices. This function 
diagnoses the time interval of status 
transition between each input of 
duplicated inputs (0.5s). 
Safety input 3 
(X4-T4, X5-T5) 
Safety input 4 
(X6-T6, X7-T7) 
Safety input 5 
(X10-T10, X11-T11) 
Safety input 6 
(X12-T12, X13-T13) 
Detail information  Logic functions (5-311) 
Warning
For connected control devices, refer to “SAFETY PRECAUTIONS”. 
Safety check signals (pulses signals) are sent from the drive terminals (T4 to T13) to diagnose 
connected safety devices and input circuits. Safety check signals can not be used as a power supply 
for connected devices. 
Note. If there are unused safety inputs in safety input 1 and safety input 2, connect the unused receive 
terminals (Xn) to a 24V DC power supply (V+). If they are not connected, the SafetyOne does 
not turn ON the safety outputs. 
Note. Solid state outputs, such as safety light curtains, can not be connected to safety input 3 to safety 
input 6. 
Note. Use safety input 3 through safety input 6 as specified combinations, such as receive terminal 
(Xn) and drive terminal (Tn). If the combinations are incorrect, SafetyOne does not work 
correctly. 
Note. If there are unused safety inputs in safety input 3 through safety input 6, connect the unused 
receive terminals (Xn) to the corresponding drive terminals (Tn). If they are not connected, the 
SafetyOne does not turn ON the safety outputs. 