Owner manual
Warning 
z  Do not connect devices having input and output specifications that do not satisfy the 
requirements of the SafetyOne. 
Refer to the following for information on the requirements of connected devices. 
Connected Control Device  Requirements 
Emergency stop switch 
Device equipped with a direct opening action mechanism conforming to 
IEC/EN60947-5-5 or indicated in IEC/EN60947-5-1 
Interlock switch, 
limit switch 
Device equipped with a direct opening action mechanism indicated in 
IEC/EN60947-5-1 
Interlock switch with lock  Spring lock interlock switch with solenoid 
Mode select switch 
Device conforming to regulations of the country where used and required 
categories (for example, switch conforming to IEC/EN60947-1) 
Enabling switch  Device conforming to IEC/EN60947-5-8 (or IEC/EN60947-5-1) 
Solid state output device 
Device conforming to regulations of the country where used (for example, 
safety light curtain conforming to IEC/EN61496-1) 
PNP output (See Note 1) 
Non-contact interlock switch  IDEC HS7A series 
Safety relay  Relay equipped with forced guide mechanism or conforming to EN50205 
Contactor 
(electromagnetic switch) 
Contactor equipped with forced guide mechanism 
Other control devices 
Use start switches and other devices that conform to the regulations of the 
country where used. 
Muting sensor 
Device conforming to IEC/EN60947-5-2 as shown below 
-3 wire transmission (dark on) photoelectric switch which has a PNP open 
collector output. 
-3 wire (normal open) proximity switch which has a PNP open collector 
output. 
Muting lamp 
Incandescent bulb indicator light conforming to IEC/EN60947-1 or 
IEC/EN60947-5-1 
Note 2: It is not possible to detect a disconnection of the muting lamp when 
using an LED indicator light. 
Input device for two-hand 
control 
Device witch the structure conforming to ISO13851, and consists of 
momentary switches conforming to IEC/EN 60947-5-1 with NO/NC contacts.
z  Make sure that the end-user thoroughly understands the contents of this user’s manual. 
Note 1. SafetyOne reads input data at regular intervals. Use a solid state output device that sends 
output signals of the waveforms shown below. Otherwise the SafetyOne cannot process the input 
signal correctly. 
Applicable solid state 
output device 
Pulse output off cycle of 40ms or 
more and an off time of 1ms or less.
Pulse output off time of 0.5ms or 
less. 
(Waveform of solid sate 
output) 
The device may not be usable even if the above specifications are satisfied. Be sure to 
thoroughly confirm operations using the actual device. 
Off cycle: 40ms or more 
Off time:   
1ms or less
Off time: 0.5ms or less