Owner manual

BASIC OPERATIONS
4-7
Chapter 4
3. Confirm the configuration and press the
enter button.
Confirm that the selected timer switch matches
the blinking timer LED, and then press the enter
button by using the configuration tool.
Be sure to confirm that they match. If the switch
configuration and display do not match and you
press the enter button, an unintended delay timer
may be activated.
Press and hold the enter button for 1 to 5s to
activate the configuration. "C" blinks in the error
LED display while you press the enter button. If
you press the enter button for less than 1s or
more than 5s, the timer is not activated.
4. Confirm that the timer is activated.
The timer LED light changes from a blinking
display to solid display, the error LED display
turns off, and the selected timer value is activated.
After configuring the timer, be sure to confirm that
the selected timer value is activated.
5. Close and lock the protective cover.
Close the protective cover.
Refer to "Using the protective cover" for details.
To protect the configuration setting, it is
recommended that the protective cover be locked.
0
.1 .5 1 2 5 15 30
SAFE-IN
TIMER(S)
SAFE-OUT
SOLENOID
-OUT
START-IN
X0 X1
X2 X3
X4
X5
X6 X7
X10 X11
X12 X13
X14
X15
X16
X17
Y0 Y1
Y2 Y3
Y17 Y20
LOGIC
ERROR
TYPE :
0
.1 .5 1 2 5 15 30
SAFE-IN
TIMER(S)
SAFE-OUT
SOLENOID
-OUT
START-IN
X0 X1
X2 X3
X4
X5
X6 X7
X10 X11
X12 X13
X14
X15
X16
X17
Y0 Y1
Y2 Y3
Y17 Y20
LOGIC
ERROR
TYPE :
(Blinking)
Fig. 4.9 Confirmation of timer switch
configuration and LED indication
(
Confi
g
uration state
)
Fig. 4.10 LED indication during enter
button is valid
(
Confi
g
uration state
)
(Blinking)
(Blinking)
Fig. 4.11 Completion the configuration
of OFF-delay timer value ā€œ2sā€œ
(Run state)
0
.1 .5 1 2 5 15 30
SAFE-IN
TIMER(S)
SAFE-OUT
SOLENOID
-OUT
START-IN
X0 X1
X2 X3
X4
X5
X6 X7
X10 X11
X12 X13
X14
X15
X16
X17
Y0 Y1
Y2 Y3
Y17 Y20
LOGIC
ERROR
TYPE :