Owner manual
LOGIC 
5-326 
External device monitoring input 
This function is for monitoring external devices controlled by the SafetyOne. External devices can 
be diagnosed for errors by connecting a NC contact, such as a contactor or a safety relay. As 
shown in Fig. 5-17, this function is comprised of an input receiving circuit (X
n
), drive circuit (T
n
), and 
functional output. 
Fig. 5-17 Circuit for external device monitor input function 
Connects to 
NC contact on devices such as a contactor, safety relay, or other devices equipped with forced 
guided mechanisms 
Note. Solid state output devices cannot be connected. 
Description of operation 
I
    When a safety check signal from the drive circuit is supplied correctly to the receiving circuit, 
the output is turned ON. (Ex. External device is turned OFF.) 
II
 When safety check signal input to the receiving circuit is turned OFF, the output is turned OFF. 
(Ex. External device is turned ON.) 
III
 If the safety check signal is not supplied correctly to the receiving circuit due to an error in an 
external device or input circuit, the output is turned OFF immediately. Status of the detected 
error is displayed on error LED, input LED, and monitor output. (Ex. Fault in external device 
or wiring error) 
Error detection function 
Noise detection filter 
The SafetyOne is tested acording to IEC/EN 61000-6-2, however in the case when the SafetyOne 
is used in an environment with severe noise, the SafetyOne changes to the Stop state and displays 
"9" on the error LED display. 
Note. Refer to “Safety output without timer” or to “Safety output with timer” for details of EDM input 
monitoring. 
X
n
T
n
External device 
I
n
External Device
Mon itor
EDM