Owner manual
LOGIC 
5-262 
Functions (Logic 105) 
●Safety inputs: X0 to X11 
Safety inputs are used to diagnose the status of connected safety devices, such as emergency 
stop switches, and interlock switches. 
Intended inputs 
(Terminal names) 
Function 
Function name  Dual channel safety input 
Symbol 
Dual Channel Safety
Description of operation  This function diagnoses the status of 
connected safety devices. This 
function diagnoses the time interval of 
status transition between each input of 
duplicated inputs (0.1s). The function 
does not use drive terminals (T0 to 
T11). 
Safety input 1 
(X0, X1) 
Safety input 2 
(X2, X3) 
Safety input 3 
(X4, X5) 
Safety input 4 
(X6, X7) 
Safety input 5 
(X10, X11) 
Detail information  Logic functions (5-317) 
Warning
For connected control devices, refer to “SAFETY PRECAUTIONS”. 
Note. If safety inputs are not used, connect the receive terminals to a 24V DC power supply (V+). If 
they are not connected, the SafetyOne does not turn ON the safety outputs. 