Owner manual
LOGIC
5-205
Chapter 5
●State monitor outputs: Y14 to Y16
State monitor outputs are used to output the internal state of SafetyOne.
State Intended outputs
(Terminal names)
Initial Run Configuration Protection Stop
State monitor output 1
(Y14)
ON
OFF
OFF
OFF
ON
State monitor output 2
(Y15)
ON
OFF
ON
ON
ON
or
OFF
State monitor output 3
(Y16)
OFF
ON
OFF
OFF
OFF
Refer to “Chapter 4 BASIC OPERATIONS” and to “Chapter 6 TROUBLE SHOOTING” for details of
each state.
Warning
The monitor outputs are not safety outputs. Do not use these to construct a safety system.
Caution
Refer to "Chapter 2 PRODUCT SPECIFICATIONS" for specifications of each input and output.